Overload protection - 283722

Overload Relay Series 8550
Art. No.: 283722

Product Type: 8550/1-OL-GLS3-E10-80-95-11
Product Description: Overload protection
min. ambient temperature: -25 °C
max. ambient temperature: +60 °C
Class 1 Division / Zone: Division 2 / Zone 1
Zone Filter: 2 G | Gb | Zone 13 G | Gc | Zone 23 G | Gc | Zone 2
Product variant: with auxiliary contacts
Certificates: ATEX (FM), Canada (FM), IECEx (FM), USA (FM)
Trigger class: Class E10
Rated operational voltage: 690 V
Rated operational current: 20 - 80 A
Main contacts: 3-pole
Auxiliary contacts: 2 (1 NO + 1 NC)
Connection cross-section: 25 - 95 mm²
Connection cross section AWG: 4 to 4/0 AWG
Country of origin: DE
More information

Technical data

General

MY R. STAHL 8550B
Product variant with auxiliary contacts
Product Type 8550/1-OL-GLS3-E10-80-95-11
Highlights Modular component for overload monitoring of motors up to 37 kW / 50 hp at 400/480 V
The electronic relay is sensitive to a fluctuating ambient temperature
Large clamping range for main terminals
Tripping class E5, E10, E20 and E30 can be selected via type code
Integrated earth protection
Greater adjustment range of the overload trigger from 20 to 80 A
Integrated reset button and electronic reset via 24 V DC control
Functional Description The electronic overload relay for R. STAHL's 8550 series is a component for load current monitoring of motors. It reliably reports an overload and safely shuts off the motor using a contactor. Together with the moulded case circuit breaker in the same series which is also available, these three components form a motor starter which reliably control powers up to 37 kW / 50 hp at 400 or 480 V (other powers available on request). Earth fault protection is also integrated, meaning that Ex d and Ex e motors are safely protected at all points. The broad adjustment range of the overload current optimises the variety of versions. Resetting in case of error is either done manually on the unit on-site via the integrated reset button, or electrically via the control system.

Explosion Protection

Electrical Data

Ambient Conditions

Mechanical Data

Mounting / Installation

Commercial data

Downloads

Description Document Type Language
Overload protection - 8550/1-OL-GLS3-E10-80-95-11 - 283722 - en-US Single Data Sheet
pdf
Overload Relay - 8550 - de-DE Product Overview
pdf
Overload Relay - 8550 - en-GB Product Overview
pdf
Overload Relay - 8550 - fr-FR Product Overview
pdf
Overload Relay - 8550 - es-ES Product Overview
pdf
Overload Relay - 8550 - en-US Product Overview
pdf
Overload protection - 8550/1-OL-GLS3-E10-80-95-11 - 283722 - de-DE Single Data Sheet
pdf
Overload protection - 8550/1-OL-GLS3-E10-80-95-11 - 283722 - en-GB Single Data Sheet
pdf
Overload protection - 8550/1-OL-GLS3-E10-80-95-11 - 283722 - fr-FR Single Data Sheet
pdf
Overload protection - 8550/1-OL-GLS3-E10-80-95-11 - 283722 - es-ES Single Data Sheet
pdf

Ask our Experts

Previous

Contact form

*Mandatory fields
Previous

We'll be glad to call you back to support you.

Wir rufen Sie gerne für ein Beratungsgespräch zurück. EN
*Mandatory